🎉 Free launch period — every calculator, every feature unlocked, no account needed, through mid-November 2026. PDF reports carry a watermark for everyone during this period.

Generator Paralleling / Synchronization Check

Voltage, frequency and phase-angle difference between an incoming generator and the bus/system, checked against adjustable acceptance windows before closing the paralleling breaker.

AAJappsEngineering Calculation Report

Generator Paralleling / Synchronization Check

Sync-check (ANSI device 25) style acceptance windows — adjustable

Generated

For preliminary engineering use only — always verify results against project-specific standards and a qualified engineer's review before use in a real design.

Generator & bus readings

V
V
Hz
Hz
°

Acceptance windows (adjustable)

%
Hz
°

Synchronization check

Voltage difference0.73%
Frequency difference0.050 Hz
Beat period20.0 s
Phase angle
Safe to closeYES