Harmonic Analysis Calculator

IEEE 519-2014 Table 1 (voltage) & Table 2 (current, TDD-referenced to max demand load current IL) distortion limit checks. Full per-order breakdown table and K-factor estimate are subscriber features.

AAJappsEngineering Calculation Report

Harmonic Analysis Calculator

IEEE 519-2014 Table 1 & 2

Generated

For preliminary engineering use only — always verify results against project-specific standards and a qualified engineer's review before use in a real design.

System basis

kV
A
A

Voltage harmonic spectrum (% of fundamental)

%
%
%
%
%
%
%
%

Current harmonic spectrum (% of I1)

%
%
%
%
%
%
%
%

Full breakdown & K-factor

Subscriber
See the full per-order table and K-factor estimate in the results panel to the right.

Voltage distortion (Table 1)

VTHD2.80% (limit 8%)
Worst individual orderh5 = 2.00%
Individual limitlimit 5%

Current distortion (Table 2, TDD)

ITHD6.66%
TDD5.33% (limit 8%)
Worst individual orderh5 = 4.00% of IL
Individual limitlimit 7.00%

Full breakdown & K-factor

h20.5% of I₁ (0.40% of IL vs 1.75% limit)
h33% of I₁ (2.40% of IL vs 7.00% limit)
h55% of I₁ (4.00% of IL vs 7.00% limit)
h72.5% of I₁ (2.00% of IL vs 7.00% limit)
h91% of I₁ (0.80% of IL vs 7.00% limit)
h111.5% of I₁ (1.20% of IL vs 3.50% limit)
h130.8% of I₁ (0.64% of IL vs 3.50% limit)
Approx. K-Factor1.147