IDMT Earth Fault Relay Setting (50N/51N)

Earth-fault variant of the IDMT overcurrent relay — same IEC 60255-151 / IEEE C37.112 curve mathematics, applied to a residual/earth-fault CT circuit, plus an optional high-set instantaneous stage.

AAJappsEngineering Calculation Report

IDMT Earth Fault Relay Setting (50N/51N)

IEC 60255-151 / IEEE C37.112

Generated

For preliminary engineering use only — always verify results against project-specific standards and a qualified engineer's review before use in a real design.

Earth Fault Relay (50N/51N)

Fault current & instantaneous stage

A
A
s

Earth fault relay response

Relay (secondary) current7.50 A
Plug setting multiplier37.50×
IDMT operating time0.372 s
Instantaneous stageDoes not operate