๐ŸŽ‰ Free launch period โ€” every calculator, every feature unlocked, no account needed, through mid-November 2026. PDF reports carry a watermark for everyone during this period.
NEC 430.32 / IEC 60947-4-19 min read

Worked Example: Overload, Contactor and Ground-Fault Settings for a 34 A Motor

Three independent protection settings for the same motor โ€” overload trip class chosen from its starting time, contactor size from its duty, and ground-fault pickup from the system's earthing arrangement.

Scenario

Motor full-load current34 A
Service factor / temp rise markingStandard (not โ‰ฅ1.15 SF or โ‰ค40ยฐC rise)
Starting time8 seconds
Duty classS1 โ€” continuous running
Starts per hour4
Contactor dutyAC-3 (normal start/stop)
System groundingSolidly grounded

Step-by-step calculation

Step 1: Set the overload relay pickup

Without a high-service-factor or low-temperature-rise nameplate marking, NEC 430.32 defaults to the more conservative 115% setting.

settingA = FLA x 115%
34 x 1.15
settingA = 39.1 A

Step 2: Select the overload relay trip class from starting time

IEC 60947-4-1 trip classes are named for their maximum trip time (seconds) at 7.2x rated current โ€” a longer starting time needs a trip class that tolerates that duration without nuisance tripping during a normal start.

Step 3: Check whether thermal memory (electronic overload) is required

Required if duty class is S4/S5, or starts/hour > 15
S1 duty, 4 starts/hour โ€” neither condition met
A standard bimetal overload relay is adequate; thermal memory not required

Step 4: Size the contactor

AC-3 duty (normal motor starting/stopping) uses the motor's FLA directly, with no additional multiplier.

requiredEquivalentA = FLA (AC-3)
34 A required -> rounds up to the next standard contactor frame, 40 A

Step 5: Set ground-fault pickup for the solidly grounded system

pickupA = max(20% x FLA, 5 A)
max(0.2 x 34, 5) = max(6.8, 5)
pickupA = 6.8 A, fast definite-time delay (0.1 s)

Result summary

CheckRequirementActualStatus
Overload relay settingn/a (this is the sizing result)39.1 A, Trip Class 10โœ“ PASS
Contactor sizeโ‰ฅ 34 A (AC-3)40 A standard frameโœ“ PASS
Ground-fault pickupn/a (this is the sizing result)6.8 A, 0.1 s delayโœ“ PASS
This motor's protection scheme calls for a 39.1 A overload set to Trip Class 10, a 40 A AC-3 contactor, and a fast (0.1 s) ground-fault trip at 6.8 A โ€” three independent settings, each driven by a different characteristic of the motor and its installation.

Key insight: Overload trip class and contactor duty rating solve two completely different problems โ€” trip class is about tolerating a normal motor start's inrush without nuisance tripping, while contactor rating is about the switching duty of making and breaking the circuit itself. A motor with a long starting time and light switching duty (or vice versa) can need very different combinations of these two settings, which is why they're sized independently rather than from one single number.

Try it with your own numbers

Every input in this example is editable in the live calculator โ€” free, no signup.

Open Motor Protection Sizer calculator โ†’

Frequently asked questions

What would change with AC-4 (jogging/reversing) contactor duty instead of AC-3?

AC-4 duty applies a 2.0x conservative multiplier to the required equivalent current (a rule-of-thumb, not a single universal standard ratio, since it's genuinely manufacturer/model specific) โ€” for this 34 A motor, that would push the requirement to 68 A, jumping to an 80 A standard contactor frame instead of 40 A, reflecting the much more severe electrical wear of frequent jogging or plugging duty compared to normal start/stop.

Why does an HRG (high-resistance grounded) system need a completely different ground-fault approach?

On a solidly grounded system, ground faults draw high current that a simple percentage-of-FLA pickup can reliably detect quickly. HRG systems are deliberately designed to limit ground-fault current to a small, controlled charging current โ€” so ground-fault pickup instead has to be set relative to that system's own charging current (roughly 2x it) with a longer alarm/delayed-trip time, since the goal on an HRG system is often to alarm and allow orderly shutdown rather than instantly trip.

More in Motors & Drives

โ† Back to all worked examples